Heatcraft Refrigeration Products Air-Cooled Condensers none User Manual Page 8

  • Download
  • Add to my manuals
  • Print
  • Page
    / 20
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 7
8
Start-Up
Check for proper fan rotation. Air is drawn through the coil on all
units. Be sure the fans turn freely.
Rotation of the motors and blades should be in a “CW direction
looking at the unit from the blade side. On three phase units, it
may be necessary to reverse two of the three power leads to the
unit.
NOTE: The manifold assembly is not designed to
support eld piping. Any damages to the
condenser due to excessive weight,
pressure or vibration will not be covered
by our standard warranty.
Discharge Gas Pulsation
Gas pulsations in a refrigeration system are most commonly
associated with the compressor and connecting discharge
piping. Variations in the system piping conguration, line sizing,
operating pressures and compressor and component mounting
all contribute to the presence and magnitude of these pulsations.
The vibration and movement of components caused by the
pulsations may result in line breakage or damage to the
condenser. In order to eliminate discharge pulsations and the
potential for related condenser damage, it is recommended
that a discharge muer be installed in the refrigeration
piping. In all cases, the recommendations of the compressor or
muer manufacturer must be followed when selecting these
components.
Fan Cycling
A decrease in ambient air temperature results in a capacity
increase in the air-cooled condenser. This capacity increase is
directly proportional to the temperature dierence between the
condensing temperature and the temperature of the ambient
air entering the condenser. Since air-cooled condensers are
often required to operate over a wide range of ambient air
temperatures and variable loading conditions, provisions must
be made to maintain the overall system balance. Any air-cooled
condenser tends to run at a low head pressure when operating in
a low ambient air temperature. Low head pressures could result in
poor expansion valve operation and poor system operation.
The cycling of condenser fans provides an automatic means of
maintaining head pressure control, within reasonable limits, at
lower ambient air temperatures. A fan cycling control system
allows fans to cycle in sequence by sensing either ambient
temperature or condensing pressures. However, care must
be used by the engineer or installing contractor in making
adjustments to prevent short cycling of the fan motors. Short
cycling is normally caused by too close a dierential in the control
settings or set points. If ooding valves are used with fan cycling,
they must be set to follow the fan cycling.
Recommended dierential settings for ambient sensing
thermostats are 5° F and a minimum of 35 PSIG dierential for
pressure switches. However, system or climate conditions vary
and the controls may require further eld adjustment to provide
optimum system performance and prevent short cycling.
Any fan cycle that is less than three minutes is considered short
cycling, and could be detrimental to the system. Adjust controls
accordingly. It is also recommended that the fan closest to the
header end of the condenser be wired to run continuously,
whenever the compressor(s) is (are) operational. Cycling all of
the fans o usually results in rapid, short cycling of the fans and
erratic head pressure control.
If additional head pressure control is necessary beyond letting the
lead fan run, we recommend adding variable speed or ooding
controls. If cycling the header fan is necessary for adequate head
pressure control, we recommend cycling on pressure. Ambient
sensing thermostats should never be used to cycle the lead fan.
Fans must not cycle in multiples except on double wide single
circuit condensers where they may cycle in pairs (one motor on
each side). Do not cycle more than two fans at a time on double
wide condensers and only one fan at a time on single wide
condensers.
Operation
Winter Operation Head Pressure Control
The capacity of an air-cooled condenser varies with the dierence
between the entering air dry bulb temperature and the
condensing temperature of the refrigerant. Since air temperature
in some regions varies as much as 100° from summer to winter,
some means must be employed to keep the condensing
temperature suciently high to insure proper operation of the
refrigerant expansion valve during low ambient operation, and
also allow sucient capacity so that excessively high condensing
temperatures do not result during high ambient conditions.
The low limit of the head pressure is dependent upon the
required pressure drop across the thermostatic expansion valve.
For normal air conditioning applications, head pressure should
be maintained above a condensing temperature corresponding
to 90° F. This, in eect, corresponds to a normal lower limit of
about 60° F ambient air. Since air conditioning is not normally
required at these lower ambient temperatures, condenser head
pressure control may not always be necessary. However for those
applications which are of such a nature that operation is required
below 60° F ambient air temperature, additional head pressure
control will be required.
Page view 7
1 2 3 4 5 6 7 8 9 10 11 12 13 ... 19 20

Comments to this Manuals

No comments