Heatcraft Refrigeration Products Air-Cooled Condensers none User Manual Page 5

  • Download
  • Add to my manuals
  • Print
  • Page
    / 20
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 4
5
Typical Arrangements
Figure 1 illustrates a typical piping arrangement involving a
remote condenser located at a higher elevation, as commonly
encountered when the condenser is on a roof and the compressor
and receiver are on grade level or in a basement equipment
room.
In this case, the design of the discharge line is very critical. If
properly sized for full load condition, the gas velocity might be
too low at reduced loads to carry oil up through the discharge
line and condenser coil. Reducing the discharge line size would
increase the gas velocity suciently at reduced load conditions;
however, when operating at full load, the line would be greatly
undersized, and thereby create an excessive refrigerant pressure
drop. This condition can be overcome in one of two following
ways:
1. The discharge line may be properly sized for the desired
pressure drop at full load conditions and an oil separator
installed at the bottom of the trap in the discharge line
from the compressor.
2. A double riser discharge line may be used as shown in
Figure 2. Line A should be sized to carry the oil at minimum
load conditions and the line “B” should be sized so
that at the full load conditions both lines would have
sucient ow velocity to carry the oil to the condenser.
For more complete information, refer to the ASHRAE Handbook
on Systems.
Figure 1
Figure 2
Notes:
1. All oil traps are to be as short in radius as
possible. Common practice is to fabricate the
trap using three 90 degrees ells.
2. Pressure relief valves are recommended at the
condenser for protection of the coil.
3. A drain line check valve is recommended for
applications where the condenser may be at a
lower temperature than the receiver.
Installation, Refrigerant Piping
Install piping according to standard accepted refrigeration
practice. The following recommendations should be adhered to:
1. See Tables 1 and 2 for discharge and liquid
drain line sizes for remote condenser
connections.
2. Use only refrigeration grade copper tubing.
3. Soft solder joints are not acceptable.
4. Put dry nitrogen through lines while brazing.
5. Do not leave dehydrated piping or components
open to the atmosphere any longer than is
absolutely necessary.
Page view 4
1 2 3 4 5 6 7 8 9 10 ... 19 20

Comments to this Manuals

No comments