10
Table 3. Minimum Ambient for Fan Cycling
Number of Fans
Single Double Design T.D.*
Row Row 30 25 20 15 10
2 4 35 45 55 60 70
3 6 15 30 40 55 65
4 8 0 15 30 45 60
5 10 0 10 20 35 55
6 / 7 12 / 14 0 0 10 30 50
* Based on maintaining 90°F minimum condensing temperature.
Table 4. Mechanical Fan Cycling Thermostat Settings
Number of Fans
Single Double Design Thermostat Setting
Row Rows T.D. 1 2 3 4 5
2 4 30 60
25 65
20 70
15 75
10 80
3 6 30 60 40
25 65 55
20 70 60
15 75 65
10 80 65
4 8 30 60 50 30
25 65 55 40
20 70 65 50
15 75 70 60
10 80 75 70
5 10 30 60 55 45 30
25 65 60 50 35
20 70 65 60 40
15 75 70 65 55
10 80 75 70 65
6 / 7 12 / 14 30 55 50 40 30 25
25 65 60 55 45 35
20 70 65 60 50 40
15 75 70 65 60 50
10 80 75 70 65 60