General Maintenance Schedule
(Service/Maintenance should be performed only by a
qualified / certified refrigeration service technician.)
Weekly
Check refrigerant charge using the liquid line sight glass.
Check compressor oil level.
Check compressor crankcase heater operation.
Check main power and control voltage
Check appearance of area around the unit.
Check system pressures
Monthly
Check the refrigerant system for leaks.
Check suction filters and liquid line filter driers.
Check all flanged connection bolts, fittings and line
clamps for tightness.
Inspect condenser fan blades and motor mounts for
cracks, loose set screws or mounting bolts.
Tighten all electrical connections.
Check operation and condition of contacts on
compressor / fan motor contactors. Check appearance of
control panel interior.
Check appearance of exterior conduit / junction boxes.
Check appearance of insulation.
Check operation of auxiliary equipment.
Quarterly
With unit in stable operation, record all operating conditions:
Suction / discharge / liquid refrigerant pressure(s) and
temperature(s)
System superheat, liquid subcooling, ambient
temperature
Compressor amperage
Test all operating and safety controls.
Annually
Obtain oil sample for analysis. Change oil if required.
Clean condenser coil.
Straighten condenser fins as required.
Change liquid line filter drier and suction filter cores.
Note: The above information is provided only
as a general guideline to aid servicing
personnel and equipment owners in
maintaining equipment. Due to vari-
ables in the actual equipment
application, operating conditions, and
environment recommended service
intervals may vary.